Motor Full-load Current
kW/HP থেকে FLC ও DOL Starting Current
Full-load Current (FLC)
27.7A
15 kW · 3-phase · 400 V
DOL Starting Current (আনুমানিক)
180A
6.5 × FLC
Input / Apparent power
16.3 kW
19.2 kVA
η = 0.921 ও cos φ = 0.85 ধরা হয়েছে (15 kW, 4-pole motor-এর সাধারণ মান)। Nameplate-এর মান জানলে Advanced mode-এ দিন।
1. Input power
P ÷ η = 15 ÷ 0.921
= 16.2866 kW
2. Apparent power
Input ÷ cos φ = 16.287 ÷ 0.85
= 19.1608 kVA
3. Full-load current
15 × 1000 ÷ (√3 × 400 × 0.921 × 0.85)
= 27.6562 A
4. DOL starting current (আনুমানিক)
27.656 × 6.5
= 179.7651 A
FLC = P × 1000 ÷ (√3 × V × η × cos φ); 1-phase-এ √3 নেই।